Reinforcement Learning-assisted Voltage Stability Analysis of the Nigerian Power Grid Using Dynamic Voltage Restorer (DVR) and Battery Energy Storage System (BESS)
Ndifreke U. Ekanem, Mfonobong A. Umoren, Kufre M. Udofia
Journal of Engineering Research and Reports · pp. 286–304 · Published 19 Jun 2025
10.9734/jerr/2025/v27i61545Abstract
This study proposed and validated a reinforcement learning (RL)-assisted framework to enhance voltage stability in Nigeria’s power grid through dynamic coordination of a Dynamic Voltage Restorer (DVR) and Battery Energy Storage System (BESS). Addressing the Nigerian grid’s vulnerabilities—including ageing infrastructure, frequent voltage sags/swells, and inadequate reactive power support—the framework integrated a Deep Deterministic Policy Gradient (DDPG)-based RL controller with classical voltage stability methodologies rooted in Newton-Raphson power flow, Jacobian matrix eigenvalue analysis, and voltage stability indices (L-Index, VCPI). A realistic 3-bus MATLAB/Simulink model of the Alaoji-Onitsha 330kV transmission corridor was developed, simulating fault-induced instability scenarios with a 500 MVA generator, 800 MW + 300 MVAR industrial load, and transmission line parameters reflective of Nigeria’s grid. The RL agent was trained to minimise voltage deviations and harmonic distortion, and dynamically optimised DVR voltage injection and BESS charge/discharge cycles achieved a 3.25 ms response time of 0.92 p.u. voltage compensation, and a 96% reduction in total harmonic distortion (THD from 9.06% to 0.36%). Comparative analyses demonstrated the RL controller’s superiority over conventional PI, ANN, and PSO methods, with 75% faster transient recovery and 71% lower THD. Empirical validation under IEC 61000-4-30 and IEEE 519-2022 standards confirmed stable voltage regulation within ±0.9% of nominal during asymmetrical faults, while Jacobian eigenvalue analysis revealed a 40% improvement in stability margins (smallest singular value, σ_min, increased by a factor of 2.8). Through the combination of model-free RL adaptability with physics-based grid modelling, the study provided an adaptable solution for weak grids, reducing dependency on pre-trained datasets and offering a cost-effective strategy for mitigating voltage instability in Nigeria’s power system amid growing renewable integration and load volatility.
Cited by 2
2 citations reported by external sources — individual citing-article records aren't available to list yet.
Related research
- A Comparison of Generalized Unified Power Flow Controller and Load Tap Changing Transformer for Voltage Stability Enhancement in a Power System — shares topic coverage
- Enhancing Dynamic Stability of Solar PV Micro Grid Clusters Via Genetic Algorithm Optimized Adaptive Droop Control and Tie-line Stabilization — shares topic coverage
- Optimal Siting and Sizing of Distributed Generators for Voltage Stability Enhancement Using a Particle Swarm Optimization Framework — shares topic coverage
- Machine-Learning Prediction of Weak Buses and Optimal SVC Placement for Voltage Stability Improvement on the Transmission Network with Special Emphasis on Nigeria — shares topic coverage
- Voltage Quality Analysis on Power Transmission Networks: A Case Study of 330kV Power Transmission Networks in Nigeria — shares topic coverage
Article metrics
Real usage data collected on this platform.
25
Page views
0
PDF downloads
4
Outbound clicks
2
Citations
Views over time
Views by country
Approximate, from request IP at view time — not citizenship or institution. Countries with fewer than 5 views are grouped as "Other".
Traffic sources
Referring site, by host.
Views and downloads exclude known bots/crawlers. Citations combines this platform's own DOI-resolved index with each external source's own reported total — see Cited by above for individually listed citing works. Last refreshed 0 seconds ago.