Skip to content
Research Article Open access CC BY 4.0

Design of 22KW LPG Burner for an Oil Refinery Boiler

B. S. Kinigoma, G. O. Ani

Journal of Scientific Research and Reports · pp. 70–79 · Published 19 Mar 2020

10.9734/jsrr/2020/v26i230226

Abstract

The oil refining process is energy-intensive since every aspect of the process consumes energy. The need to minimize energy consumption when raising steam in boilers using Liquefied Petroleum Gas (LPG) burner was the focus of this study, to proffer techniques for improving optimum thermal efficiency via proper burner design and positioning. Burner design models were utilized to evaluate parameters for optimum combustion, to deliver the expected thermal output, including thermal efficiency. The results of this study suggest that, to design a 22KW LPG burner for an oil refinery boiler, the optimum values estimated for the burner parameters for efficient combustion at a gas flow rate of 1.89x10-4m3/sec, including Wobbe Index (83285.7KJ/m3), size of burner nozzle (1.9 mm), gas supply pressure (0.80 psi), length of burner slot for air entrainment (137.61 mm), size of burner pipe (46.48 mm), total orifice diameter (400.53 mm), and number of 3 mm. Studies elsewhere also suggest that if a proper angle between the burner axis and the boiler surface is achieved, significant changes in the amount of gas used can results positively in the direction of fuel utilization efficiency, thereby saving the cost of steam production in an LPG fired refinery boiler.

Burner design nozzle diameter burner slot burner orifice Wobbe index liquefied petroleum gas

Cited by 1

FEATURES OF THE USE OF LIQUEFIED PETROLEUM GAS AS A RESERVE AND ALTERNATIVE FUEL AT COAL-BASED CHP PLANTS

M.V. Сhernyavskyy, Ye.S. Miroshnychenko, O.Yu. Provalov · Energy Technologies & Resource Saving · 2022

Article metrics

Real usage data collected on this platform.

0

Page views

0

PDF downloads

0

Outbound clicks

1

Citations

Views by country

Approximate, from request IP at view time — not citizenship or institution. Countries with fewer than 5 views are grouped as "Other".

No views recorded yet.

Traffic sources

Referring site, by host.

No traffic recorded yet.

Views and downloads exclude known bots/crawlers. Citations combines this platform's own DOI-resolved index with each external source's own reported total — see Cited by above for individually listed citing works. Last refreshed 0 seconds ago.